APPLICATION: Fire Survival Cables are used in emergency and life-safety systems where electrical circuits must remain operational during a fire. They are widely installed in fire alarm systems, emergency lighting, smoke extraction systems, sprinkler systems, public address systems, evacuation systems, hospitals, airports, metro stations, commercial buildings, industrial facilities, and other critical infrastructure requiring uninterrupted operation under fire conditions.
| Parameter | Specification |
|---|---|
| Conductor | Annealed Copper |
| Fire Barrier | Mica Tape |
| Insulation | Fire Resistant Silicone Rubber / Special Compound |
| Core Configuration | Single Core / Multicore |
| Outer Sheath | LSZH / Flame Retardant PVC |
| Voltage Rating | 300/500 V, 600/1000 V |
| Fire Resistance | Maintains Circuit Integrity During Fire |
| Smoke Emission | Low Smoke |
| Halogen Content | Zero Halogen (LSZH) |
| Application | Fire Alarm, Emergency Lighting & Life Safety Systems |
| Cross Sectional Area of Conductor (Nom.) | Thickness of Insulation | Dia. Of Armour Wire | Overall Diameter (App.) | ||
|---|---|---|---|---|---|
| 2 Core | 3 Core | 4 Core | |||
| (Sq mm) | (mm) | (mm) | (mm) | (mm) | (mm) |
| 1.5 | 0.6 | 0.90 | 13.0 | 13.5 | 14.8 |
| 32.5 | 0.7 | 0.90 | 14.5 | 15.0 | 16.0 |
| 4 | 0.7 | 0.90 | 15.5 | 16.5 | 17.8 |
| 6 | 0.7 | 1.25 | 17.0 | 17.5 | 20.0 |
| 10 | 0.7 | 1.25 | 19.0 | 20.5 | 22.0 |
| 16 | 0.7 | 1.25 | 21.0 | 22.5 | 24.5 |
| 25 | 0.9 | 1.60 | 22.5 | 26.5 | 28.5 |
| 35 | 0.9 | 1.60 | 24.0 | 29.0 | 31.5 |
| 50 | 1.0 | 1.60 | 26.5 | 29.5 | 33.2 |
| 70 | 1.1 | 2.00 | 30.0 | 33.0 | 39.2 |
| 95 | 1.1 | 2.00 | 34.0 | 38.0 | 43.2 |