APPLICATION: Power cables for energy supply are installed outdoors, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected.
CONSTRUCTION:
| Technical Data: | Max. Operating Temperature : 90°C |
| Rated Voltage: | 1100 v / 600/1000 v |
| Specifications : | IS 1554 (PVC), IS 7098 (XLPE), BS 5467 |
| Range: | 3/3.5/4C X 1.5 – 400 mm2 |
| Size (mm²) | Insulation PVC Thickness Min. (mm) | Inner Sheath PVC Thickness Min. (mm) | Armour Size in mm (G.I.) W | Armour Size in mm (G.I.) H | Outer Sheath PVC Thickness Min. (mm) | Approx. Outer Sheath O/D (mm) | Approx. Weight of Cable (kg/km) | Max DC Conductor Resistance at 20°C (Ohm/km) | Current Rating Direct in Ground (Amp) | Current Rating In Air (Amp) |
|---|---|---|---|---|---|---|---|---|---|---|
| 3C x 1.5 | 0.80 | 0.30 | 1.40 | 1.24 | 1.24 | 13.20 | 377 | 12.10 | 21 | 17 |
| 3C x 2.5 | 0.90 | 0.30 | 1.40 | 1.24 | 1.24 | 14.40 | 454 | 7.41 | 27 | 24 |
| 3C x 4 | 1.00 | 0.30 | 1.40 | 1.24 | 1.24 | 16.50 | 603 | 4.61 | 36 | 30 |
| 3C x 6 | 1.00 | 0.30 | 1.40 | 1.40 | 1.40 | 17.90 | 720 | 3.08 | 45 | 39 |
| 3C x 10 | 1.00 | 0.30 | 4.00 | 0.80 | 1.40 | 18.85 | 828 | 1.83 | 60 | 52 |
| 3C x 16 | 1.00 | 0.30 | 4.00 | 0.80 | 1.40 | 21.00 | 1092 | 1.15 | 77 | 66 |
| 3C x 25 | 1.20 | 0.30 | 4.00 | 0.80 | 1.40 | 21.60 | 1270 | 0.727 | 99 | 90 |
| 3C x 35 | 1.20 | 0.30 | 4.00 | 0.80 | 1.40 | 23.50 | 1602 | 0.524 | 120 | 110 |
| 3C x 50 | 1.40 | 0.30 | 4.00 | 0.80 | 1.40 | 26.85 | 2141 | 0.387 | 145 | 135 |
| 3C x 70 | 1.40 | 0.40 | 4.00 | 0.80 | 1.56 | 29.95 | 2762 | 0.268 | 175 | 165 |
| 3C x 95 | 1.60 | 0.40 | 4.00 | 0.80 | 1.56 | 33.90 | 3636 | 0.193 | 210 | 200 |
| 3C x 120 | 1.60 | 0.40 | 4.00 | 0.80 | 1.56 | 36.55 | 4438 | 0.153 | 240 | 230 |
| 3C x 150 | 1.80 | 0.50 | 4.00 | 0.80 | 1.72 | 40.60 | 5448 | 0.124 | 270 | 265 |
| 3C x 185 | 2.00 | 0.50 | 4.00 | 0.80 | 1.98 | 44.50 | 6555 | 0.0991 | 300 | 305 |
| 3C x 240 | 2.20 | 0.60 | 4.00 | 0.80 | 2.04 | 49.60 | 8220 | 0.0754 | 345 | 355 |
| 3C x 300 | 2.40 | 0.60 | 4.00 | 0.80 | 2.20 | 54.70 | 10112 | 0.0601 | 385 | 400 |
| 3C x 400 | 2.60 | 0.70 | 4.00 | 0.80 | 2.35 | 61.60 | 13208 | 0.0470 | 425 | 455 |
| RADICAB 1.1 kV 3 CORE COPPER CONDUCTOR PVC INSULATED , INNER SHEATHED ARMOURED PVC SHEATHED CABLES (IS : 1554 PART 1) CABLE CODE : YWYNFY |
|||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| SIZE (MM2) | INSULATION PVC THICKNESS IN MM (NOM.) | INNER SHEATH PVC THICKNESS IN MM (MIN.) | ARMOUR SIZE IN MM (G.I) | OUTER SHEATH PVC THICKNESS IN MM (MIN.) | APPROX OUTER SHEATH O/D IN MM | APPROX WEIGHT OF CABLE (KGS./KM) | MAX. DC CONDUCTOR RESISTANCE at 20° C (Ohm/Km) | Current Ratings (Amp.) | |||
| MAIN CORE | HALF CORE | W | H | Direct In Ground | In Air | ||||||
| 3.5C X 25 | 0.90 | 0.70 | 0.30 | 4.0 | 0.80 | 1.40 | 22.70 | 1424 | 0.727 | 120 | 125 |
| 3.5C X 35 | 0.90 | 0.70 | 0.30 | 4.0 | 0.80 | 1.40 | 24.50 | 1748 | 0.524 | 145 | 155 |
| 3.5C X 50 | 1.00 | 0.90 | 0.30 | 4.0 | 0.80 | 1.56 | 28.50 | 2391 | 0.387 | 170 | 190 |
| 3.5C X 70 | 1.10 | 0.90 | 0.40 | 4.0 | 0.80 | 1.50 | 32.15 | 3108 | 0.268 | 210 | 235 |
| 3.5C X 95 | 1.10 | 1.00 | 0.40 | 4.0 | 0.80 | 1.56 | 36.10 | 4082 | 0.193 | 250 | 290 |
| 3.5C X 120 | 1.20 | 1.10 | 0.50 | 4.0 | 0.80 | 1.72 | 40.50 | 5135 | 0.153 | 285 | 330 |
| 3.5C X 150 | 1.40 | 1.10 | 0.50 | 4.0 | 0.80 | 1.88 | 44.10 | 6137 | 0.124 | 315 | 375 |
| 3.5C X 185 | 1.60 | 1.10 | 0.60 | 4.0 | 0.80 | 2.04 | 49.15 | 7542 | 0.0991 | 355 | 435 |
| 3.5C X 240 | 1.70 | 1.20 | 0.70 | 4.0 | 0.80 | 2.20 | 54.60 | 9433 | 0.0754 | 410 | 510 |
| 3.5C X 300 | 1.80 | 1.40 | 0.80 | 4.0 | 0.80 | 2.36 | 60.40 | 11567 | 0.0601 | 460 | 590 |
| 3.5C X 400 | 2.00 | 1.60 | 0.80 | 4.0 | 0.80 | 2.52 | 68.10 | 14983 | 0.0470 | 520 | 670 |
| 3.5C X 500 | 2.20 | 1.70 | 1.00 | 4.0 | 0.80 | 2.84 | 76.10 | 18699 | 0.0366 | 580 | 750 |
| RADICAB 1.1 kV 4 CORE COPPER CONDUCTOR PVC INSULATED , INNER SHEATHED ARMOURED PVC SHEATHED CABLES as : 1554 PART 1) CABLE CODE : YWY/YFY |
||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Size (mm²) | Insulation PVC Thickness Min. (mm) | Inner Sheath PVC Thickness Min. (mm) | Armour Size in mm (G.I.) | Outer Sheath PVC Thickness Min. (mm) | Approx. Outer Sheath O/D (mm) | Approx. Weight of Cable (kg/km) | Max. DC Conductor Resistance at 20°C (Ohm/km) | Current Ratings (Amp.) | ||
| W | H | Direct In Ground | In Air | |||||||
| 4C x 1.5 | 0.80 | 0.30 | 1.40 | – | 1.24 | 14.10 | 446 | 12.10 | 21 | 17 |
| 4C x 2.5 | 0.90 | 0.30 | 1.40 | – | 1.24 | 15.40 | 544 | 7.41 | 27 | 24 |
| 4C x 4 | 1.00 | 0.30 | 1.40 | – | 1.40 | 18.15 | 750 | 4.61 | 36 | 30 |
| 4C x 6 | 1.00 | 0.30 | 1.40 | – | 1.40 | 18.20 | 778 | 3.08 | 45 | 39 |
| 4C x 10 | 1.00 | 0.30 | 4.00 | 0.80 | 1.40 | 20.55 | 1041 | 1.83 | 60 | 52 |
| 4C x 16 | 1.00 | 0.30 | 4.00 | 0.80 | 1.40 | 23.20 | 1398 | 1.15 | 77 | 66 |
| 4C x 25 | 1.20 | 0.30 | 4.00 | 0.80 | 1.40 | 25.65 | 1690 | 0.727 | 99 | 90 |
| 4C x 35 | 1.20 | 0.30 | 4.00 | 0.80 | 1.56 | 28.55 | 2168 | 0.524 | 120 | 110 |
| 4C x 50 | 1.40 | 0.40 | 4.00 | 0.80 | 1.56 | 32.70 | 2904 | 0.387 | 145 | 135 |
| 4C x 70 | 1.40 | 0.40 | 4.00 | 0.80 | 1.56 | 36.15 | 3698 | 0.268 | 175 | 165 |
| 4C x 95 | 1.60 | 0.40 | 4.00 | 0.80 | 1.72 | 41.45 | 4813 | 0.193 | 210 | 200 |
| 4C x 120 | 1.60 | 0.50 | 4.00 | 0.80 | 1.88 | 45.20 | 6030 | 0.153 | 240 | 230 |
| 4C x 150 | 1.80 | 0.50 | 4.00 | 0.80 | 2.04 | 49.95 | 7370 | 0.124 | 270 | 265 |
| 4C x 185 | 2.00 | 0.60 | 4.00 | 0.80 | 2.20 | 55.10 | 8916 | 0.0991 | 300 | 305 |
| 4C x 240 | 2.20 | 0.60 | 4.00 | 0.80 | 2.35 | 61.20 | 11137 | 0.0754 | 345 | 355 |
| 4C x 300 | 2.40 | 0.70 | 4.00 | 0.80 | 2.52 | 67.70 | 13715 | 0.0601 | 385 | 400 |
| 4C x 400 | 2.60 | 0.70 | 4.00 | 0.80 | 2.84 | 76.75 | 17961 | 0.0470 | 425 | 455 |